Three 6.6 kV, 3-ϕ, 10 MVA alternators are connected to a common bus. Each alternator has a positive negative and zero sequence reactances as 0.15 p.u., 0.1 p.u.,0.05 p.u. respectively. A single line to ground fault occurs at point F, as shown in figure below.



If is the fault current when all the alternator neutrals solidy grouned If is the fault current when only one neutral is solidly grounded and other two neutrals are isolated. Then the value of |IfIf|=________kA.
  1. 6.512

tuteeHUB earn credit +10 pts


( 5 ) 1 Rating

Report

Posted on 20 Nov 2024, this text provides information on Power Systems related to Other. Please note that while accuracy is prioritized, the data presented might not be entirely correct or up-to-date. This information is offered for general knowledge and informational purposes only, and should not be considered as a substitute for professional advice.